Standard Electro Mechanical - Actuator and Wiring Details
Actuator Options
Control Options are available in 24V AC/DC or 230V AC, 24V 0-10v modulating and pneumatic operation. For further details, please refer to the FSD Series product literature.
The damper control options are powered from the control panel.
24/230V option wiring:
The control options are complete with two 1m flying leads. One 2 core plus earth for power and one 6 core for indication.
The 6 core are from the auxiliary switch to give open/closed indication.
S1 and S4 are the common and are linked
S2 gives closed indication at the point of 5° to fully closed
S6 gives open indication at the point of 80° to fully open
S3 and S5 are not used and thus should be isolated
This will effect a requirement for a 5 core cable.
Wiring Detail
Refer to schematic of typical BSB electro mechanical system shown on Page 5.
Cable and Carrier System Selection to be the responsibility of the electrical contractor, in line with the project specification and site requirements.
Commissioning: BSB offers a comprehensive after sales service including pre-commission checks or a complete commissioning service of all our products in line with current CIBSE guidelines as well as planned preventative maintenance.